Data records

Each statement in Motor Testing Reference is recorded as a data record with its source, verification date, review status and history. The index lists 94 records by subject.

Test methods

Bolted connection resistance

Data records for Bolted connection resistance.
RecordStatement
tests.bolted-connection-resistance.equipment.motor.acceptanceBolted Connection Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.1 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.bolted-connection-resistance.equipment.motor.maintenanceBolted Connection Resistance is specified for AC induction motors and generators in maintenance testing at clause 7.15.1.B.1 of ANSI/NETA MTS-2023. Value: AC induction motors and generators.

Commutator Bar to Bar Resistance

Data records for Commutator Bar to Bar Resistance.
RecordStatement
tests.commutator-bar-to-bar-resistance.equipment.motor.acceptanceCommutator Bar to Bar Resistance is specified for DC motors and generators in acceptance testing at clause 7.15.3.B.6 of ANSI/NETA ATS-2025. Value: DC motors and generators.
tests.commutator-bar-to-bar-resistance.governed-by.ansi-neta-atsCommutator Bar to Bar Resistance is addressed in ANSI/NETA ATS-2025.
tests.commutator-bar-to-bar-resistance.titleThe test method is named Commutator Bar to Bar Resistance. Value: Commutator Bar to Bar Resistance.

Contact resistance

Data records for Contact resistance.
RecordStatement
tests.contact-resistance.equipment.motor.acceptanceContact Resistance is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.6 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters.
tests.contact-resistance.equipment.motor.maintenanceContact Resistance is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.7 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters.

Control and functional verification

Data records for Control and functional verification.
RecordStatement
tests.control-and-functional-verification.equipment.motor.acceptanceControl and Functional Verification is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.12 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.control-and-functional-verification.equipment.motor.maintenanceControl and Functional Verification is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Dielectric withstand

Data records for Dielectric withstand.
RecordStatement
tests.dielectric-withstand.equipment.motor.acceptanceDielectric Withstand is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.3 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.dielectric-withstand.equipment.motor.maintenanceDielectric Withstand is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Field Pole Voltage Drop

Data records for Field Pole Voltage Drop.
RecordStatement
tests.field-pole-voltage-drop.equipment.motor.acceptanceField Pole Voltage Drop is specified for synchronous motors and generators in acceptance testing at clause 7.15.2.B.15 of ANSI/NETA ATS-2025. Value: synchronous motors and generators.
tests.field-pole-voltage-drop.equipment.motor.maintenanceField Pole Voltage Drop is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.field-pole-voltage-drop.governed-by.ansi-neta-atsField Pole Voltage Drop is addressed in ANSI/NETA ATS-2025.
tests.field-pole-voltage-drop.governed-by.ansi-neta-mtsField Pole Voltage Drop is addressed in ANSI/NETA MTS-2023.
tests.field-pole-voltage-drop.titleThe test method is named Field Pole Voltage Drop. Value: Field Pole Voltage Drop.

Fuse resistance

Data records for Fuse resistance.
RecordStatement
tests.fuse-resistance.equipment.motor.acceptanceFuse Resistance is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.8 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters.
tests.fuse-resistance.equipment.motor.maintenanceFuse Resistance is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.9 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters.

Insulated Bearing Insulation Resistance

Data records for Insulated Bearing Insulation Resistance.
RecordStatement
tests.insulated-bearing-insulation-resistance.equipment.motor.acceptanceInsulated Bearing Insulation Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.8 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.insulated-bearing-insulation-resistance.equipment.motor.maintenanceInsulated Bearing Insulation Resistance is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.insulated-bearing-insulation-resistance.governed-by.ansi-neta-atsInsulated Bearing Insulation Resistance is addressed in ANSI/NETA ATS-2025.
tests.insulated-bearing-insulation-resistance.governed-by.ansi-neta-mtsInsulated Bearing Insulation Resistance is addressed in ANSI/NETA MTS-2023.
tests.insulated-bearing-insulation-resistance.titleThe test method is named Insulated Bearing Insulation Resistance. Value: Insulated Bearing Insulation Resistance.

Insulation power factor dissipation factor

Data records for Insulation power factor dissipation factor.
RecordStatement
tests.insulation-power-factor-dissipation-factor.equipment.motor.acceptanceInsulation Power Factor Dissipation Factor is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.5 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.insulation-power-factor-dissipation-factor.equipment.motor.maintenanceInsulation Power Factor Dissipation Factor is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Insulation resistance

Data records for Insulation resistance.
RecordStatement
tests.insulation-resistance.equipment.generator.acceptanceInsulation Resistance is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.B.1 of ANSI/NETA ATS-2025. Value: engine-generator emergency systems.
tests.insulation-resistance.equipment.generator.maintenanceInsulation Resistance is specified for engine-generator emergency systems in maintenance testing at clause 7.22.1.B.1 of ANSI/NETA MTS-2023. Value: engine-generator emergency systems.
tests.insulation-resistance.equipment.motor.acceptanceInsulation Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.2 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.insulation-resistance.equipment.motor.maintenanceInsulation Resistance is specified for AC induction motors and generators in maintenance testing at clause 7.15.1.B.2 of ANSI/NETA MTS-2023. Value: AC induction motors and generators.

Motor Current Signature Analysis

Data records for Motor Current Signature Analysis.
RecordStatement
tests.motor-current-signature-analysis.equipment.motor.acceptanceMotor Current Signature Analysis is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.15 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.motor-current-signature-analysis.equipment.motor.maintenanceMotor Current Signature Analysis is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.motor-current-signature-analysis.governed-by.ansi-neta-atsMotor Current Signature Analysis is addressed in ANSI/NETA ATS-2025.
tests.motor-current-signature-analysis.governed-by.ansi-neta-mtsMotor Current Signature Analysis is addressed in ANSI/NETA MTS-2023.
tests.motor-current-signature-analysis.titleThe test method is named Motor Current Signature Analysis. Value: Motor Current Signature Analysis.

Motor Run Test Under Load

Data records for Motor Run Test Under Load.
RecordStatement
tests.motor-run-test-under-load.equipment.motor.acceptanceMotor Run Test Under Load is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.14 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.motor-run-test-under-load.equipment.motor.maintenanceMotor Run Test Under Load is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.motor-run-test-under-load.governed-by.ansi-neta-atsMotor Run Test Under Load is addressed in ANSI/NETA ATS-2025.
tests.motor-run-test-under-load.governed-by.ansi-neta-mtsMotor Run Test Under Load is addressed in ANSI/NETA MTS-2023.
tests.motor-run-test-under-load.titleThe test method is named Motor Run Test Under Load. Value: Motor Run Test Under Load.

Motor Vibration Analysis

Data records for Motor Vibration Analysis.
RecordStatement
tests.motor-vibration-analysis.equipment.generator.acceptanceMotor Vibration Analysis is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.B.5 of ANSI/NETA ATS-2025. Value: engine-generator emergency systems.
tests.motor-vibration-analysis.equipment.generator.maintenanceMotor Vibration Analysis is specified for engine-generator emergency systems in maintenance testing at clause 7.22.1.B.4 of ANSI/NETA MTS-2023. Value: engine-generator emergency systems.
tests.motor-vibration-analysis.equipment.motor.acceptanceMotor Vibration Analysis is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.13 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.motor-vibration-analysis.equipment.motor.maintenanceMotor Vibration Analysis is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.motor-vibration-analysis.governed-by.ansi-neta-atsMotor Vibration Analysis is addressed in ANSI/NETA ATS-2025.
tests.motor-vibration-analysis.governed-by.ansi-neta-mtsMotor Vibration Analysis is addressed in ANSI/NETA MTS-2023.
tests.motor-vibration-analysis.titleThe test method is named Motor Vibration Analysis. Value: Motor Vibration Analysis.

Partial discharge offline

Data records for Partial discharge offline.
RecordStatement
tests.partial-discharge-offline.equipment.motor.acceptancePartial Discharge Offline is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.16 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.partial-discharge-offline.equipment.motor.maintenancePartial Discharge Offline is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Phase rotation and phasing

Data records for Phase rotation and phasing.
RecordStatement
tests.phase-rotation-and-phasing.equipment.generator.acceptancePhase Rotation and Phasing is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.B.3 of ANSI/NETA ATS-2025. Value: engine-generator emergency systems.

Polarity test

Data records for Polarity test.
RecordStatement
tests.polarity-test.equipment.motor.acceptancePolarity Test is specified for DC motors and generators in acceptance testing at clause 7.15.3.B.7 of ANSI/NETA ATS-2025. Value: DC motors and generators.

Power factor tip up

Data records for Power factor tip up.
RecordStatement
tests.power-factor-tip-up.equipment.motor.acceptancePower Factor Tip Up is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.6 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.power-factor-tip-up.equipment.motor.maintenancePower Factor Tip Up is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Resistor and coil resistance

Data records for Resistor and coil resistance.
RecordStatement
tests.resistor-and-coil-resistance.equipment.motor.acceptanceResistor and Coil Resistance is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.7 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters.
tests.resistor-and-coil-resistance.equipment.motor.maintenanceResistor and Coil Resistance is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.8 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters.

Rtd circuit verification

Data records for Rtd circuit verification.
RecordStatement
tests.rtd-circuit-verification.equipment.motor.acceptanceRTD Circuit Verification is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.11 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.rtd-circuit-verification.equipment.motor.maintenanceRTD Circuit Verification is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Surge arrester and spd tests

Data records for Surge arrester and spd tests.
RecordStatement
tests.surge-arrester-and-spd-tests.equipment.motor.acceptanceSurge Arrester and SPD Tests is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.9 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.surge-arrester-and-spd-tests.equipment.motor.maintenanceSurge Arrester and SPD Tests is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Surge Comparison Test

Data records for Surge Comparison Test.
RecordStatement
tests.surge-comparison-test.equipment.motor.acceptanceSurge Comparison Test is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.7 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.surge-comparison-test.equipment.motor.maintenanceSurge Comparison Test is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.surge-comparison-test.governed-by.ansi-neta-atsSurge Comparison Test is addressed in ANSI/NETA ATS-2025.
tests.surge-comparison-test.governed-by.ansi-neta-mtsSurge Comparison Test is addressed in ANSI/NETA MTS-2023.
tests.surge-comparison-test.titleThe test method is named Surge Comparison Test. Value: Surge Comparison Test.

Synchronous Machine Field Application

Data records for Synchronous Machine Field Application.
RecordStatement
tests.synchronous-machine-field-application.equipment.motor.acceptanceSynchronous Machine Field Application is specified for synchronous motors and generators in acceptance testing at clause 7.15.2.B.18 of ANSI/NETA ATS-2025. Value: synchronous motors and generators.
tests.synchronous-machine-field-application.equipment.motor.maintenanceSynchronous Machine Field Application is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.
tests.synchronous-machine-field-application.governed-by.ansi-neta-atsSynchronous Machine Field Application is addressed in ANSI/NETA ATS-2025.
tests.synchronous-machine-field-application.governed-by.ansi-neta-mtsSynchronous Machine Field Application is addressed in ANSI/NETA MTS-2023.
tests.synchronous-machine-field-application.titleThe test method is named Synchronous Machine Field Application. Value: Synchronous Machine Field Application.

Vacuum interrupter integrity

Data records for Vacuum interrupter integrity.
RecordStatement
tests.vacuum-interrupter-integrity.equipment.motor.acceptanceVacuum Interrupter Integrity is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.5 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters.
tests.vacuum-interrupter-integrity.equipment.motor.maintenanceVacuum Interrupter Integrity is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.6 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters.

Vacuum interrupter mac test

Data records for Vacuum interrupter mac test.
RecordStatement
tests.vacuum-interrupter-mac-test.equipment.motor.acceptanceVacuum Interrupter MAC Test is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.3 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters.
tests.vacuum-interrupter-mac-test.equipment.motor.maintenanceVacuum Interrupter MAC Test is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.4 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters.

Visual and mechanical inspection

Data records for Visual and mechanical inspection.
RecordStatement
tests.visual-and-mechanical-inspection.equipment.generator.acceptanceVisual and Mechanical Inspection is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.A of ANSI/NETA ATS-2025. Value: engine-generator emergency systems.
tests.visual-and-mechanical-inspection.equipment.generator.maintenanceVisual and Mechanical Inspection is specified for engine-generator emergency systems in maintenance testing at clause 7.22.1.A of ANSI/NETA MTS-2023. Value: engine-generator emergency systems.
tests.visual-and-mechanical-inspection.equipment.motor.acceptanceVisual and Mechanical Inspection is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.A of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.visual-and-mechanical-inspection.equipment.motor.maintenanceVisual and Mechanical Inspection is specified for AC induction motors and generators in maintenance testing at clause 7.15.1.A of ANSI/NETA MTS-2023. Value: AC induction motors and generators.

Winding resistance

Data records for Winding resistance.
RecordStatement
tests.winding-resistance.equipment.motor.acceptanceWinding Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.4 of ANSI/NETA ATS-2025. Value: AC induction motors and generators.
tests.winding-resistance.equipment.motor.maintenanceWinding Resistance is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators.

Standards

IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery

Data records for IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery.
RecordStatement
std.ieee-43.approvedThe 2013 edition of IEEE 43 was approved on 2013-12-11. Value: 2013.
std.ieee-43.designationIEEE 43-2013 is the designation of the document titled IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery. Value: IEEE 43-2013.
std.ieee-43.edition.2013IEEE 43-2013 is the 2013 edition of the IEEE document titled IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery, published on 2014-03-06. Value: 2013.
std.ieee-43.revision-ofIEEE 43-2013 is a revision of IEEE 43-2000. Value: 2013.
std.ieee-43.scopeThe recommended practice describes direct-voltage procedures for measuring the insulation resistance and polarization index of stator and rotor windings and explains how to interpret the results.
std.ieee-43.sponsorIEEE 43-2013 was sponsored by the Electric Machinery Committee of the IEEE Power and Energy Society.
std.ieee-43.statusThe IEEE catalog lists IEEE 43-2013 with the status Inactive-Reserved Standard, with an inactivation date of 2024-03-21. Value: Inactive-Reserved Standard.
std.ieee-43.structure.annex-aAnnex A of IEEE 43-2013 is informative and describes variants of the polarization index.
std.ieee-43.structure.conditionsClause 7 of IEEE 43-2013 covers the conditions recorded at the time of test, and clause 8 covers the winding connections used for the test.
std.ieee-43.structure.factorsClause 6 of IEEE 43-2013 covers the factors that affect insulation resistance readings, among them surface condition, moisture, temperature and test voltage.
std.ieee-43.structure.instrumentsClause 9 of IEEE 43-2013 describes the instruments and methods for measuring insulation resistance.
std.ieee-43.structure.interpretationClause 11 of IEEE 43-2013 covers the interpretation of test results, and clause 12 gives recommended minimum values.
std.ieee-43.structure.procedureClause 5 of IEEE 43-2013 sets out the insulation resistance and polarization index test procedures and the choice of test voltage.
std.ieee-43.structure.safetyClause 4 of IEEE 43-2013 deals with safety during insulation resistance testing.
std.ieee-43.structure.voltage-applicationClause 10 of IEEE 43-2013 covers how the test voltage is applied and held, including allowance for the drop across a protective resistor.
std.ieee-43.titleThe publisher catalog gives the full title of IEEE 43-2013 as IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery. Value: IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery.