Data records
Each statement in Motor Testing Reference is recorded as a data record with its source, verification date, review status and history. The index lists 94 records by subject.
Test methods
Bolted connection resistance
| Record | Statement |
|---|---|
| tests.bolted-connection-resistance.equipment.motor.acceptance | Bolted Connection Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.1 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.bolted-connection-resistance.equipment.motor.maintenance | Bolted Connection Resistance is specified for AC induction motors and generators in maintenance testing at clause 7.15.1.B.1 of ANSI/NETA MTS-2023. Value: AC induction motors and generators. |
Commutator Bar to Bar Resistance
| Record | Statement |
|---|---|
| tests.commutator-bar-to-bar-resistance.equipment.motor.acceptance | Commutator Bar to Bar Resistance is specified for DC motors and generators in acceptance testing at clause 7.15.3.B.6 of ANSI/NETA ATS-2025. Value: DC motors and generators. |
| tests.commutator-bar-to-bar-resistance.governed-by.ansi-neta-ats | Commutator Bar to Bar Resistance is addressed in ANSI/NETA ATS-2025. |
| tests.commutator-bar-to-bar-resistance.title | The test method is named Commutator Bar to Bar Resistance. Value: Commutator Bar to Bar Resistance. |
Contact resistance
| Record | Statement |
|---|---|
| tests.contact-resistance.equipment.motor.acceptance | Contact Resistance is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.6 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters. |
| tests.contact-resistance.equipment.motor.maintenance | Contact Resistance is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.7 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters. |
Control and functional verification
| Record | Statement |
|---|---|
| tests.control-and-functional-verification.equipment.motor.acceptance | Control and Functional Verification is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.12 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.control-and-functional-verification.equipment.motor.maintenance | Control and Functional Verification is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Dielectric withstand
| Record | Statement |
|---|---|
| tests.dielectric-withstand.equipment.motor.acceptance | Dielectric Withstand is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.3 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.dielectric-withstand.equipment.motor.maintenance | Dielectric Withstand is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Field Pole Voltage Drop
| Record | Statement |
|---|---|
| tests.field-pole-voltage-drop.equipment.motor.acceptance | Field Pole Voltage Drop is specified for synchronous motors and generators in acceptance testing at clause 7.15.2.B.15 of ANSI/NETA ATS-2025. Value: synchronous motors and generators. |
| tests.field-pole-voltage-drop.equipment.motor.maintenance | Field Pole Voltage Drop is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.field-pole-voltage-drop.governed-by.ansi-neta-ats | Field Pole Voltage Drop is addressed in ANSI/NETA ATS-2025. |
| tests.field-pole-voltage-drop.governed-by.ansi-neta-mts | Field Pole Voltage Drop is addressed in ANSI/NETA MTS-2023. |
| tests.field-pole-voltage-drop.title | The test method is named Field Pole Voltage Drop. Value: Field Pole Voltage Drop. |
Fuse resistance
| Record | Statement |
|---|---|
| tests.fuse-resistance.equipment.motor.acceptance | Fuse Resistance is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.8 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters. |
| tests.fuse-resistance.equipment.motor.maintenance | Fuse Resistance is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.9 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters. |
Insulated Bearing Insulation Resistance
| Record | Statement |
|---|---|
| tests.insulated-bearing-insulation-resistance.equipment.motor.acceptance | Insulated Bearing Insulation Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.8 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.insulated-bearing-insulation-resistance.equipment.motor.maintenance | Insulated Bearing Insulation Resistance is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.insulated-bearing-insulation-resistance.governed-by.ansi-neta-ats | Insulated Bearing Insulation Resistance is addressed in ANSI/NETA ATS-2025. |
| tests.insulated-bearing-insulation-resistance.governed-by.ansi-neta-mts | Insulated Bearing Insulation Resistance is addressed in ANSI/NETA MTS-2023. |
| tests.insulated-bearing-insulation-resistance.title | The test method is named Insulated Bearing Insulation Resistance. Value: Insulated Bearing Insulation Resistance. |
Insulation power factor dissipation factor
| Record | Statement |
|---|---|
| tests.insulation-power-factor-dissipation-factor.equipment.motor.acceptance | Insulation Power Factor Dissipation Factor is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.5 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.insulation-power-factor-dissipation-factor.equipment.motor.maintenance | Insulation Power Factor Dissipation Factor is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Insulation resistance
| Record | Statement |
|---|---|
| tests.insulation-resistance.equipment.generator.acceptance | Insulation Resistance is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.B.1 of ANSI/NETA ATS-2025. Value: engine-generator emergency systems. |
| tests.insulation-resistance.equipment.generator.maintenance | Insulation Resistance is specified for engine-generator emergency systems in maintenance testing at clause 7.22.1.B.1 of ANSI/NETA MTS-2023. Value: engine-generator emergency systems. |
| tests.insulation-resistance.equipment.motor.acceptance | Insulation Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.2 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.insulation-resistance.equipment.motor.maintenance | Insulation Resistance is specified for AC induction motors and generators in maintenance testing at clause 7.15.1.B.2 of ANSI/NETA MTS-2023. Value: AC induction motors and generators. |
Motor Current Signature Analysis
| Record | Statement |
|---|---|
| tests.motor-current-signature-analysis.equipment.motor.acceptance | Motor Current Signature Analysis is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.15 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.motor-current-signature-analysis.equipment.motor.maintenance | Motor Current Signature Analysis is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.motor-current-signature-analysis.governed-by.ansi-neta-ats | Motor Current Signature Analysis is addressed in ANSI/NETA ATS-2025. |
| tests.motor-current-signature-analysis.governed-by.ansi-neta-mts | Motor Current Signature Analysis is addressed in ANSI/NETA MTS-2023. |
| tests.motor-current-signature-analysis.title | The test method is named Motor Current Signature Analysis. Value: Motor Current Signature Analysis. |
Motor Run Test Under Load
| Record | Statement |
|---|---|
| tests.motor-run-test-under-load.equipment.motor.acceptance | Motor Run Test Under Load is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.14 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.motor-run-test-under-load.equipment.motor.maintenance | Motor Run Test Under Load is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.motor-run-test-under-load.governed-by.ansi-neta-ats | Motor Run Test Under Load is addressed in ANSI/NETA ATS-2025. |
| tests.motor-run-test-under-load.governed-by.ansi-neta-mts | Motor Run Test Under Load is addressed in ANSI/NETA MTS-2023. |
| tests.motor-run-test-under-load.title | The test method is named Motor Run Test Under Load. Value: Motor Run Test Under Load. |
Motor Vibration Analysis
| Record | Statement |
|---|---|
| tests.motor-vibration-analysis.equipment.generator.acceptance | Motor Vibration Analysis is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.B.5 of ANSI/NETA ATS-2025. Value: engine-generator emergency systems. |
| tests.motor-vibration-analysis.equipment.generator.maintenance | Motor Vibration Analysis is specified for engine-generator emergency systems in maintenance testing at clause 7.22.1.B.4 of ANSI/NETA MTS-2023. Value: engine-generator emergency systems. |
| tests.motor-vibration-analysis.equipment.motor.acceptance | Motor Vibration Analysis is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.13 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.motor-vibration-analysis.equipment.motor.maintenance | Motor Vibration Analysis is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.motor-vibration-analysis.governed-by.ansi-neta-ats | Motor Vibration Analysis is addressed in ANSI/NETA ATS-2025. |
| tests.motor-vibration-analysis.governed-by.ansi-neta-mts | Motor Vibration Analysis is addressed in ANSI/NETA MTS-2023. |
| tests.motor-vibration-analysis.title | The test method is named Motor Vibration Analysis. Value: Motor Vibration Analysis. |
Partial discharge offline
| Record | Statement |
|---|---|
| tests.partial-discharge-offline.equipment.motor.acceptance | Partial Discharge Offline is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.16 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.partial-discharge-offline.equipment.motor.maintenance | Partial Discharge Offline is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Phase rotation and phasing
| Record | Statement |
|---|---|
| tests.phase-rotation-and-phasing.equipment.generator.acceptance | Phase Rotation and Phasing is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.B.3 of ANSI/NETA ATS-2025. Value: engine-generator emergency systems. |
Polarity test
| Record | Statement |
|---|---|
| tests.polarity-test.equipment.motor.acceptance | Polarity Test is specified for DC motors and generators in acceptance testing at clause 7.15.3.B.7 of ANSI/NETA ATS-2025. Value: DC motors and generators. |
Power factor tip up
| Record | Statement |
|---|---|
| tests.power-factor-tip-up.equipment.motor.acceptance | Power Factor Tip Up is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.6 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.power-factor-tip-up.equipment.motor.maintenance | Power Factor Tip Up is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Resistor and coil resistance
| Record | Statement |
|---|---|
| tests.resistor-and-coil-resistance.equipment.motor.acceptance | Resistor and Coil Resistance is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.7 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters. |
| tests.resistor-and-coil-resistance.equipment.motor.maintenance | Resistor and Coil Resistance is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.8 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters. |
Rtd circuit verification
| Record | Statement |
|---|---|
| tests.rtd-circuit-verification.equipment.motor.acceptance | RTD Circuit Verification is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.11 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.rtd-circuit-verification.equipment.motor.maintenance | RTD Circuit Verification is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Surge arrester and spd tests
| Record | Statement |
|---|---|
| tests.surge-arrester-and-spd-tests.equipment.motor.acceptance | Surge Arrester and SPD Tests is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.9 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.surge-arrester-and-spd-tests.equipment.motor.maintenance | Surge Arrester and SPD Tests is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Surge Comparison Test
| Record | Statement |
|---|---|
| tests.surge-comparison-test.equipment.motor.acceptance | Surge Comparison Test is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.7 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.surge-comparison-test.equipment.motor.maintenance | Surge Comparison Test is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.surge-comparison-test.governed-by.ansi-neta-ats | Surge Comparison Test is addressed in ANSI/NETA ATS-2025. |
| tests.surge-comparison-test.governed-by.ansi-neta-mts | Surge Comparison Test is addressed in ANSI/NETA MTS-2023. |
| tests.surge-comparison-test.title | The test method is named Surge Comparison Test. Value: Surge Comparison Test. |
Synchronous Machine Field Application
| Record | Statement |
|---|---|
| tests.synchronous-machine-field-application.equipment.motor.acceptance | Synchronous Machine Field Application is specified for synchronous motors and generators in acceptance testing at clause 7.15.2.B.18 of ANSI/NETA ATS-2025. Value: synchronous motors and generators. |
| tests.synchronous-machine-field-application.equipment.motor.maintenance | Synchronous Machine Field Application is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
| tests.synchronous-machine-field-application.governed-by.ansi-neta-ats | Synchronous Machine Field Application is addressed in ANSI/NETA ATS-2025. |
| tests.synchronous-machine-field-application.governed-by.ansi-neta-mts | Synchronous Machine Field Application is addressed in ANSI/NETA MTS-2023. |
| tests.synchronous-machine-field-application.title | The test method is named Synchronous Machine Field Application. Value: Synchronous Machine Field Application. |
Vacuum interrupter integrity
| Record | Statement |
|---|---|
| tests.vacuum-interrupter-integrity.equipment.motor.acceptance | Vacuum Interrupter Integrity is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.5 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters. |
| tests.vacuum-interrupter-integrity.equipment.motor.maintenance | Vacuum Interrupter Integrity is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.6 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters. |
Vacuum interrupter mac test
| Record | Statement |
|---|---|
| tests.vacuum-interrupter-mac-test.equipment.motor.acceptance | Vacuum Interrupter MAC Test is specified for medium-voltage motor starters in acceptance testing at clause 7.16.1.2.B.3 of ANSI/NETA ATS-2025. Value: medium-voltage motor starters. |
| tests.vacuum-interrupter-mac-test.equipment.motor.maintenance | Vacuum Interrupter MAC Test is specified for medium-voltage motor starters in maintenance testing at clause 7.16.1.2.B.4 of ANSI/NETA MTS-2023. Value: medium-voltage motor starters. |
Visual and mechanical inspection
| Record | Statement |
|---|---|
| tests.visual-and-mechanical-inspection.equipment.generator.acceptance | Visual and Mechanical Inspection is specified for engine-generator emergency systems in acceptance testing at clause 7.22.1.A of ANSI/NETA ATS-2025. Value: engine-generator emergency systems. |
| tests.visual-and-mechanical-inspection.equipment.generator.maintenance | Visual and Mechanical Inspection is specified for engine-generator emergency systems in maintenance testing at clause 7.22.1.A of ANSI/NETA MTS-2023. Value: engine-generator emergency systems. |
| tests.visual-and-mechanical-inspection.equipment.motor.acceptance | Visual and Mechanical Inspection is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.A of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.visual-and-mechanical-inspection.equipment.motor.maintenance | Visual and Mechanical Inspection is specified for AC induction motors and generators in maintenance testing at clause 7.15.1.A of ANSI/NETA MTS-2023. Value: AC induction motors and generators. |
Winding resistance
| Record | Statement |
|---|---|
| tests.winding-resistance.equipment.motor.acceptance | Winding Resistance is specified for AC induction motors and generators in acceptance testing at clause 7.15.1.B.4 of ANSI/NETA ATS-2025. Value: AC induction motors and generators. |
| tests.winding-resistance.equipment.motor.maintenance | Winding Resistance is specified for synchronous motors and generators in maintenance testing at clause 7.15.2.B of ANSI/NETA MTS-2023. Value: synchronous motors and generators. |
Standards
IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery
| Record | Statement |
|---|---|
| std.ieee-43.approved | The 2013 edition of IEEE 43 was approved on 2013-12-11. Value: 2013. |
| std.ieee-43.designation | IEEE 43-2013 is the designation of the document titled IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery. Value: IEEE 43-2013. |
| std.ieee-43.edition.2013 | IEEE 43-2013 is the 2013 edition of the IEEE document titled IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery, published on 2014-03-06. Value: 2013. |
| std.ieee-43.revision-of | IEEE 43-2013 is a revision of IEEE 43-2000. Value: 2013. |
| std.ieee-43.scope | The recommended practice describes direct-voltage procedures for measuring the insulation resistance and polarization index of stator and rotor windings and explains how to interpret the results. |
| std.ieee-43.sponsor | IEEE 43-2013 was sponsored by the Electric Machinery Committee of the IEEE Power and Energy Society. |
| std.ieee-43.status | The IEEE catalog lists IEEE 43-2013 with the status Inactive-Reserved Standard, with an inactivation date of 2024-03-21. Value: Inactive-Reserved Standard. |
| std.ieee-43.structure.annex-a | Annex A of IEEE 43-2013 is informative and describes variants of the polarization index. |
| std.ieee-43.structure.conditions | Clause 7 of IEEE 43-2013 covers the conditions recorded at the time of test, and clause 8 covers the winding connections used for the test. |
| std.ieee-43.structure.factors | Clause 6 of IEEE 43-2013 covers the factors that affect insulation resistance readings, among them surface condition, moisture, temperature and test voltage. |
| std.ieee-43.structure.instruments | Clause 9 of IEEE 43-2013 describes the instruments and methods for measuring insulation resistance. |
| std.ieee-43.structure.interpretation | Clause 11 of IEEE 43-2013 covers the interpretation of test results, and clause 12 gives recommended minimum values. |
| std.ieee-43.structure.procedure | Clause 5 of IEEE 43-2013 sets out the insulation resistance and polarization index test procedures and the choice of test voltage. |
| std.ieee-43.structure.safety | Clause 4 of IEEE 43-2013 deals with safety during insulation resistance testing. |
| std.ieee-43.structure.voltage-application | Clause 10 of IEEE 43-2013 covers how the test voltage is applied and held, including allowance for the drop across a protective resistor. |
| std.ieee-43.title | The publisher catalog gives the full title of IEEE 43-2013 as IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery. Value: IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery. |